Solutions for Protecting andManaging the Electrical Network
TTE 7017 Relay
TTE 7015 / 7017
Rotor earth fault relay STATIC RANGE
The object of the TTE 7015 and TTE 7017 is to detect immediately any fault on the rotor winding of a synchronous machine, in order to give an alarm and, if required, to separate the machine from the network.
They operate on the current injection principle, d.c. for the TTE 7015 and low frequency a.c., with low levels of voltage and current (maximum 20 V or 5 mA) for the TTE 7017.
Both models are supplied in a modular plug-in case type R2, which may be mounted either as a separate relay, projecting or flush mounting, or as an element in a standard 19" rack cradle.
PROTECTION FUNCTIONS
- Rotor earth fault [64R]
MAIN FEATURES
- Operating level
TTE 7015: adjustable from 1 to 2 mA
TTE 7017: adjustable from 500 to 5000 Ohm - Operating time
TTE 7015: approximately 0,3 sec
TTE 7017: <1 sec - n.2 output units (2 NO or 1 NO + 1 NC contacts for each unit)
- Hand reset mechanical operation indicator (TTE 7015)
- Hand reset mechanical and electrical (LED) operation indicator (TTE 7017)
downloads
Device | Doc Type | Lang. | Ref. | Index | |
---|---|---|---|---|---|
TTE 7000 | Leaflet | EN / FR | FA849 | B | |
TTE 7015 | User Manual | EN | M.1730 | A | |
TTE 7015 | User Manual | IT | MI.1730 | B | |
TTE 7015 | Connection/Definition Diagram | EN / FR | 9676 | B | |
TTE 7015 | Connection/Definition Diagram | EN / FR | 9801 | D | |
TTE 7017 | Connection/Definition Diagram | EN / FR | 9806 | E |