Solutions   for   Protecting   andManaging   the   Electrical   Network

ITV   7166 / 7266 / 7366 / 7466

Voltage restrained overcurrent relays

Relays in the ITV 7x66 series have been designed essentially to provide selective protection of generators in the event of over-loads and heavy internal or external faults.
These relays integrates two three-phase overcurrent units whose operating levels are function of the voltage on the terminals of the protected machine. Whilst the high-set operating unit is always of the independent time type, the low-set unit can have a time/current characteristic of dependent or independent time type, depending of the selected model.

Their modular draw-out case, type R3, may be mounted either as a separate relay, flush or projection mounting, or as an alement in a standard 19" rack cradle.

PROTECTION   FUNCTIONS

  • Voltage Restrained Overcurrent [51V]

MAIN   FEATURES

  • Nominal current: 1 or 5 A (50 or 60 Hz)
  • Nominal voltage: 100V - 110V - 120V or 380 V (50 or 60 Hz)
  • Current setting ranges: low threshold I> : 0,5 - 2 In, high threshold I>> : 1 - 8 In
  • Tripping time ITV 7166: t(I>): 0,5 - 30 sec, t(I>>): 0,1 - 3 sec
  • Tripping time ITV 7266 / 7366 / 7466: t(I>): 0,05 - 3 sec at 10Ir, t(I>>): 0,1 - 3 sec
  • Voltage unit setting range: low threshold U< : 20 - 40 - 60% Un, t(U<): 0,5 - 30 sec
  • n.2 output units (2NO or 1NO+1NC contacts for each unit)
  • n.2 indicators LED